AWG 9 voltage drop calculator
Voltage drop is current times the resistance of the round trip. For AWG 9 the resistance comes straight from the gauge definition and the conductor resistivity.
A
V
Voltage drop
1.356%
- Voltage lost in the cable
- 3.1184 V
- Voltage at the load
- 226.882 V
- Power lost as heat
- 62.37
- Resistance per metre
- 0.002 598 66 ohm/m
- Conductor area
- 6.634 19 mm2
- Longest run within 3% drop
- 66.38
Show the working
- Current = 20
- One-way run length = 30
- Supply voltage = 230
- System = 2
- Conductor = 1.724e-8
- Conductor temperature = 20
- diameter_mm = 0.127 * 92^((36 - (9)) / 39) = 2.906 36
- Conductor area = pi * 2.906 36^2 / 4 = 6.634 19
- Resistance per metre = 1.724e-8 / (6.634 19 * 1e-6) * (1 + 0.00393 * (20 - 20)) = 0.002 598 66
- Voltage lost in the cable = 2 * 20 * 0.002 598 66 * 30 = 3.118 39
- Voltage drop = 3.118 39 / 230 * 100 = 1.355 82
- Voltage at the load = 230 - 3.118 39 = 226.882
- Power lost as heat = 3.118 39 * 20 = 62.3678
- Longest run within 3% drop = 0.002 598 66 > 0 && 20 > 0 ? 230 * 0.03 / (2 * 20 * 0.002 598 66) : 0 = 66.3804
Values are shown to six significant figures here; the arithmetic itself runs on exact fractions and is only rounded where a number is printed.
Scenarios & local history
Compare a saved scenario
Recent calculations
The formula
- single phase or DC: drop = 2 x I x R per metre x one-way length
- three phase: drop = sqrt(3) x I x R per metre x one-way length
- R per metre = rho / area, corrected for temperature
The factor of two on a single-phase run is because the current goes out and comes back. A three-phase drop uses sqrt(3) because the return currents partly cancel.
This is resistive drop only. On long AC runs at high current, cable reactance adds to it.
Warm conductors have more resistance: at 70 degrees Celsius copper is about 20% more resistive than at 20.