120 mm2 cable size, resistance and voltage drop calculator

Metric cable is sized by its nominal copper cross-section, so 120 mm2 is the area itself rather than a gauge number. That makes the arithmetic direct: resistance is resistivity times length divided by area, and everything else follows from it.

A
V
kg/m3
Voltage drop over the run
0.1724V
≈ Rounded 120 mm2 cable
Drop as a percentage
0.075 % Within the usual 3% final-circuit limit
Nominal cross-section
120 mm2
Equivalent solid diameter
12.3608
Equivalent AWG Fractional. Round down to the next AWG number for the next thicker wire.
-3.49
Area in circular mils
236.823
Resistance per kilometre
0.143 667 ohm/km
Resistance of the one-way run
0.004 31 ohm
Power lost as heat
3.448 W
Conductor weight, one core
32.256
Longest run within 3% drop
1200.70
Show the working
  1. One-way run length = 30
  2. Load current = 20
  3. Supply voltage = 230
  4. Circuit = 2
  5. Conductor = 1.724e-8
  6. Conductor temperature = 20
  7. Conductor density = 8960
  8. Nominal cross-section = 120 = 120
  9. Equivalent solid diameter = sqrt(4 * 120 / pi) = 12.3608
  10. Area in circular mils = (12.3608 / 25.4)^2 * 1000 = 236.823
  11. Equivalent AWG = 36 - 39 * ln(12.3608 / 0.127) / ln(92) = -3.485 65
  12. r_per_m_20 = 1.724e-8 / (120 * 1e-6) = 0.000 143 667
  13. r_per_m = 0.000 143 667 * (1 + 0.00393 * (20 - 20)) = 0.000 143 667
  14. Resistance per kilometre = 0.000 143 667 * 1000 = 0.143 667
  15. Resistance of the one-way run = 0.000 143 667 * 30 = 0.004 31
  16. Voltage drop over the run = 2 * 20 * 0.004 31 = 0.1724
  17. Drop as a percentage = 0.1724 / 230 * 100 = 0.074 956 5
  18. Power lost as heat = 2 * 20^2 * 0.004 31 = 3.448
  19. Conductor weight, one core = 120 * 1e-6 * 30 * 8960 = 32.256
  20. Longest run within 3% drop = 230 * 0.03 / (2 * 20 * 0.000 143 667) = 1200.7

Values are shown to six significant figures here; the arithmetic itself runs on exact fractions and is only rounded where a number is printed.

Scenarios & local history

Compare a saved scenario

Recent calculations

    The formula

    • resistance = rho x length / area
    • single phase drop = 2 x I x R (out and back)
    • three phase drop = sqrt(3) x I x R (line to line)
    • temperature correction: R(T) = R(20) x (1 + 0.00393 (T - 20)) for copper

    The cross-section is nominal. IEC 60228 fixes the maximum resistance per kilometre rather than an exact area, so a real stranded conductor is slightly larger than the nominal figure and its resistance is a little above the ideal solid value computed here.

    The equivalent diameter is what a solid conductor of this area would measure. A stranded conductor of the same area is larger overall because of the gaps between strands.

    This is a voltage drop calculation, not a current rating. Ampacity depends on the insulation, the installation method, grouping and ambient temperature.

    Frequently asked

    What is 120 mm2 in AWG?

    Inverting the gauge formula gives n = 36 - 39 log_92(d / 0.127 mm), and the result is shown above. It is almost never a whole number, so pick the next lower AWG number to stay at or above the metric area.

    How long a run can 120 mm2 carry before the drop matters?

    The calculator shows the length at which the drop reaches 3% of the supply voltage for the current you entered. Halve the current and that length doubles.

    Related calculators

    Settings

    Theme

    System follows your operating system and changes with it.

    Text size
    High contrast

    Maximises text and border contrast and removes the grid background.

    Graph-paper background

    Round to
    Notation
    Thousands separators
    Decimal mark
    Nearest fraction

    Shows the result as the nearest tape-measure fraction, with the error it costs.


    Accessibility & interaction
    Reduce motion Stops interface animations even when the operating system does not.
    Underline links Keeps links visually distinct without relying on colour.
    Larger touch targets Makes buttons and form controls easier to tap.
    Shorter reading lines Limits article width for easier scanning.
    Monochrome display Removes colour as an information cue.
    Always-visible focus Makes the keyboard focus ring persistent and stronger.
    Verbose screen-reader results Announces the complete conversion equation.
    Sticky action bars Keeps converter and calculator actions within reach.
    Select values on focus Replaces a value immediately when you start typing.
    Left-handed mobile layout Moves key mobile actions toward the left thumb.

    Your data

    Settings, recent conversions and favourites live in this browser only. Nothing is sent anywhere.

    Offline library